This manual does not use message numbers for these notices: it indicates status via the LEDs on the CCU_SR unit. This applies to the KR C4 compact; for other KR C4 cabinets, consult the relevant manual.
What STA1 and STA2 indicate
In the KR C4 compact manual, STA1 corresponds to the CIB_SR's μC I/O nodes and STA2 to the FPGA nodes. Both LEDs are orange:
- Off: no supply voltage. For STA1, the manual asks you to check fuse F17-3 and, if the PWR/3.3 V LED lights up, replace the CCU_SR assembly. For STA2, check the supply at X1 and, if the PWR/3.3 V LED lights up, replace the CCU_SR assembly.
- Flashing at 1 Hz: normal state.
- Flashing at 10 Hz: initialisation phase.
- Flashing (internal error code): the manual calls for replacement of the CCU_SR assembly.
How to read this on the shop floor
- Unlike STAS1 and STAS2, here the manual does not ask you to check wiring in the event of an internal error: it points directly to replacing the CCU_SR.
- Before assuming an LED is off, it's worth checking the PWR LEDs, since the manual links them together.
- Our approach, which is a PAS guideline rather than the manufacturer's: work inside the cabinet is carried out by qualified personnel, with the manual for that specific variant to hand.
Frequently asked questions
What's the difference between STA1 and STA2?
The manual assigns them to different nodes (μC I/O and FPGA), and the "off" checks differ: fuse F17-3 for STA1 and the supply at X1 for STA2.
Does this apply to other KR C4 cabinets?
We haven't verified this: this information comes from the KR C4 compact manual.
Sources
- KR C4 compact Operating Instructions, BA KR C4 compact V14 (edition 11.09.2020), chap. 11.1, p. 186.