This manual does not use message numbers for these warnings: it indicates the state through the CCU_SR unit's LEDs. This applies to the KR C4 compact; for other KR C4 cabinets, check the relevant manual.
What STAS1 and STAS2 indicate
In the «Cabinet Control Unit Small Robot LED indication» section of the KR C4 compact manual, STAS1 corresponds to safety nodes A and STAS2 to safety nodes B. Both LEDs are orange and use the same code:
- Off: no supply voltage. The manual requires checking fuse F17-3; if the PWR/3.3 V LED lights up, replace the CCU_SR assembly.
- Flashing at 1 Hz: normal state.
- Flashing at 10 Hz: start-up phase.
- Flashing (internal error code): the manual requires checking the wiring of X309, X310 and X312. To check this, disconnect the cables from X309, X310 and X312 and power the control unit off and on. If the fault persists, replace the CCU_SR assembly.
How to read it on the shop floor
- A slow flash at 1 Hz is normal; flashing at 10 Hz is just start-up.
- The manual does not distinguish between internal error codes: it gives the same action for any error flash.
- Our view, which is a PAS guideline and not the manufacturer's: work inside the cabinet should be carried out by qualified personnel, with the variant's manual to hand.
Frequently asked questions
What does it mean if STAS1 and STAS2 are off?
According to the manual, that there is no supply voltage at those nodes: start by checking fuse F17-3.
Does this apply to other KR C4 models?
We haven't verified this: this information comes from the KR C4 compact manual. Other variants have their own manual.
Sources
- KR C4 compact Operating Instructions, BA KR C4 compact V14 (edition 11.09.2020), chap. 11.1, p. 185.