When the door of an interlocked cell is opened, the ABB controller logs a stop message. Which one depends on the cabinet: the IRC5 Single Cabinet distinguishes between the automatic stop (90205) and the general stop (90206), while the OmniCore E10 uses 90523 for both.
What the manuals say
- IRC5 Single Cabinet, Automatic Stop: with the robot in automatic mode, the interlocked door is opened with the automatic stop active. The test passes if 90205 «Auto Stop open» appears. It fails if it does not appear, or if 90225 «Auto Stop conflict» appears instead.
- IRC5 Single Cabinet, General Stop: the general stop is activated. The test passes if 90206 «General Stop open» appears. It fails if it does not appear, or if 90226 «General Stop conflict» appears instead.
- OmniCore E10: for both the automatic stop and the general stop, the test passes if 90523 «Safety Controller Protective Stop triggered» appears. It fails if it does not appear, or if 90780 «Two-channel fault in Safety Controller» appears instead.
How to read it on the shop floor
- A 90205 or 90206 when opening a guard on an IRC5, or a 90523 on an OmniCore E10, is what you'd expect: the guard has done its job.
- The conflict messages (90225, 90226) and 90780 are the ones that, according to the manual, make the test fail.
- Our rule of thumb, which is a PAS guideline rather than the manufacturer's: if the expected message does not appear when a guard is opened, the guard is not signed off until the cause is found.
Frequently asked questions
Why does the OmniCore E10 show the same message for two different stops?
That's what the E10 manual's tests state: both the automatic stop and the general stop show 90523. The manual doesn't explain why.
Does this apply to other cabinets?
We haven't checked: each cabinet has its own manual.
Sources
- Product manual IRC5, 3HAC047136-001 Rev. AH, pp. 219 and 220.
- Product manual OmniCore E10, 3HAC079399-001 Rev. S, pp. 128 and 129.